- CSCD核心中文核心科技核心
- RCCSE(A+)公路运输高质量期刊T1
- Ei CompendexScopusWJCI
- EBSCOPж(AJ)JST
地铁车站35/0.4 kV变电所接地设计探讨
收稿日期: 2015-10-26
修回日期: 2015-11-26
网络出版日期: 2016-03-02
Study on Grounding Design of 35/0.4 kV Substation in Metro Station
Received date: 2015-10-26
Revised date: 2015-11-26
Online published: 2016-03-02
厉红星 , 高 婷 . 地铁车站35/0.4 kV变电所接地设计探讨[J]. 隧道建设, 2016 , 36(2) : 206 -211 . DOI: 10.3973/j.issn.1672-741X.2016.02.013
The technical level of grounding design of stepdown substation of Metro station in China has to be improved so as to accord with the IEC standards and ChinaNational standards. In this paper, the disadvantages of multipoint grounding and the advantages of onepoint grounding are analyzed based on studying the grounding scheme of neutral point in low voltage side of stepdown substation of Metro station; and then a rational grounding scheme is proposed. The power frequency overvoltage and fault voltage of 0.4 kV system induced by grounding fault of 35 kV system and the resistance of weak current system are analyzed. It is concluded that the demand of grounding power resistance value of less than 1 Ω is irrational;the structural reinforcing bars should be used as natural grounding electrode; therefore the manual grounding network is not necessary.
/
| 〈 |
|
〉 |