隧道建设(中英文) ›› 2026, Vol. 46 ›› Issue (9): 1861-1873.DOI: 10.3973/j.issn.2096-4498.2026.09.004

• 研究与探索 • 上一篇    下一篇

风-热耦合的地下数据中心柴油发电机动力隧道通风降温风机配置仿真优化

杨玉容1, 黄宇婷1, 代少凯2, 扈金月1, 陈学文2   

  1. (1. 西南交通大学土木工程学院, 四川 成都 610031; 2. 贵州省交通规划勘察设计研究院股份有限公司, 贵州 贵阳 550081)
  • 出版日期:2026-09-20 发布日期:2026-09-20
  • 作者简介:杨玉容(1971—),女,重庆合川人,2012年毕业于西南交通大学,桥梁与隧道工程专业,博士,副教授,主要从事地下工程通风与防灾研究工作。 E-mail: 105575087@qq.com。

Optimization of Fan Configuration for Ventilation and Cooling in Underground Data Center Diesel Generator Power Tunnels Based on Air-Thermal Coupling

YANG Yurong1, HUANG Yuting1, DAI Shaokai2, HU Jinyue1, CHEN Xuewen2   

  1. (1. School of Civil Engineering, Southwest Jiaotong University, Chengdu 610031, Sichuan, China; 2. Guizhou Communications Planning Survey & Design Institute Co., Ltd., Guiyang 550081, Guizhou, China)
  • Online:2026-09-20 Published:2026-09-20

摘要: 地下数据中心柴油发电机动力隧道采用主机房全面通风降温与机柜内散热器局部强冷的风流串联式降温模式,其热负荷与机组投运数量呈动态耦合特征,散热路径复杂,风-热耦合效应显著,风机运行策略直接决定降温效果与能耗水平。现有研究缺少与之匹配的热源精细化计算与仿真施加方法,在全尺寸风网仿真与调算、多模式风机协同设计等方面存在明显不足。为此,以某数据中心柴油发电机动力隧道为研究对象,选取夏季9台机组(满负荷)运行的典型工况,建立机房室内余热与机柜散热器局部强冷负荷的定量计算方法。基于风-热耦合降温原理确定负荷与风量定量关系,采用SpaceClaim与Fluent软件,结合稳态3大控制方程与k-ε两方程湍流模型,提出2类热源在数值仿真中的空间分布施加方式,并构建包含负荷空间分配与风机设备配置的全尺寸精细化风网仿真模型及调算方法。针对既有风机设备配置,对主风机独立运行、送风机+主风机+竖井排风机协同运行2种模式的流场、温度场与能耗特性进行求解与对比分析。研究表明: 1)动力隧道内基于风流串联式降温路径的热源分解计算方法及仿真采用的热源空间加载方式合理,仿真模型与风网调算方法可行,可在现有机组运行设备及风机配置约束下精准寻优; 2)既有风机设备配置下,2种模式的优化工况均能满足环控散热要求,协同模式引风降温效果稍好,但集群风机总功耗巨大,协同引风效率低下; 3)满负荷工况建议优先采用主风机独立运行方案,并适度提高主风机功率。

关键词: 地下数据中心, 柴油发电机动力隧道, 运营通风, 集群风机, 热负荷, Fluent仿真, 风-热耦合, 能耗分析

Abstract: Diesel generator power tunnels in data centers commonly employ a series airflow cooling system that combines overall ventilation of the main equipment room with localized forced cooling provided by cabinet radiators. Under this operating mode, the thermal load varies dynamically with the number of operating generator units, while complex heat dissipation paths produce strong air-thermal coupling effects. Consequently, fan operating strategies have a significant influence on both cooling performance and energy consumption. However, existing studies lack refined methods for calculating and applying heat-source loads in numerical simulations, and limitations remain in full-scale ventilation network modeling, network adjustment, and the coordinated design and operation of multiple fans. To address these challenges, a diesel generator power tunnel in a data center was investigated under a representative summer operating condition in which nine generator units operated simultaneously at full load. A quantitative method was developed to calculate the residual indoor heat load in the engine room and the localized forced cooling load associated with cabinet radiators. Based on the air-thermal coupled cooling mechanism, the relationship between heat load and required air flow was established. SpaceClaim and Fluent were subsequently employed to develop a numerical simulation framework based on steady-state governing equations and the k-ε turbulence model, with spatially distributed loading methods proposed for the two heat-source types. A full-scale, high-resolution ventilation network model was then established, incorporating spatial heat load allocation and fan configuration. The two modes were compared in terms of airflow characteristics, temperature distributions, and energy consumption. The results indicate that: (1) The proposed heat-source decomposition method, based on the series airflow cooling path, and the corresponding spatial loading approach provide a reasonable representation of thermal loads in power tunnels. The developed simulation model and ventilation network adjustment method enable effective optimization while accounting for constraints associated with existing generator and fan configurations. (2) Under the existing fan equipment configuration, optimized operating conditions for both modes satisfy the required environmental control and heat dissipation criteria. Although coordinated fan control provides a slightly improved induced-air cooling effect, it results in substantially higher total fan power consumption and relatively low cooperative ventilation efficiency. (3) Under full load operating conditions, independent operation of the main fans is recommended, with an appropriate increase in mainfan capacity to further improve cooling performance.


Key words: underground data center, diesel generator power tunnel, operational ventilation, fan system, heat load, Fluent simulation, air-thermal coupling, energy consumption analysis