• 中国科学引文数据库(CSCD)来源期刊
  • 中文核心期刊中文科技核心期刊
  • Scopus RCCSE中国核心学术期刊
  • 美国EBSCO数据库 俄罗斯《文摘杂志》
  • 《日本科学技术振兴机构数据库(中国)》
二维码

隧道建设(中英文) ›› 2020, Vol. 40 ›› Issue (9): 1314-1323.DOI: 10.3973/j.issn.2096-4498.2020.09.010

• 研究与探索 • 上一篇    下一篇

苏通GIL综合管廊工程盾构隧道管片结构安全性评估#br#

苏昂1, 封坤2, *, 王宁华3, 张晓阳3, 涂新斌3, 何川2, 钱玉华3, 梁坤2   

  1. 1. 江苏省交通工程建设局, 江苏 南京〓210000 2. 西南交通大学 交通隧道工程教育部重点实验室, 四川 成都〓610031 3. 国家电网有限公司, 北京〓100031
  • 出版日期:2020-09-20 发布日期:2020-10-10
  • 作者简介:苏昂(1992—),男,江苏邳州人,2019年毕业于西南交通大学,桥梁与隧道工程专业,硕士,助理工程师,从事高速公路和水下隧道建设管理工作。 E-mail: suang1992@163.com。*通信作者: 封坤, windfeng813@163.com。
  • 基金资助:
    国家电网重点研究项目(SHJJGC1700023)

Safety Evaluation of Shield Tunnel Segment Structure of Sutong GIL Utility Tunnel Project

SU Ang1, FENG Kun2, *, WANG Ninghua3, ZHANG Xiaoyang3, TU Xinbin3, HE Chuan2, QIAN Yuhua3, LIANG Kun2   

  1.  (1. Jiangsu Provincial Transportation Engineering Construction Bureau, Nanjing 210000, Jiagnsu, China; 2. Key Laboratory of Transportation Tunnel Engineering, Ministry of Education, Southwest Jiaotong University, Chengdu 610031, Sichuan, China 3. State Grid Corporation of China, Beijing 100031, China
  • Online:2020-09-20 Published:2020-10-10

摘要: 为了探明高水压作用下大断面盾构隧道管片结构的安全性,依托苏通GIL综合管廊工程项目,选择5个控制断面作为研究对象,利用多功能盾构隧道结构体加载装置,对管片结构开展原型加载试验; 基于混凝土结构偏心受压极限承载力理论,推导出管片结构的M-N承载力曲线,并提出管片结构的安全性评价指标。研究表明: 管片结构的弯矩呈现出“蝶状”分布,轴力呈现出“圆状”分布,最大正弯矩和最大轴力均出现在拱顶位置; 5个控制断面管片结构的试验内力均在承载力曲线包络范围内,管片结构均处于安全状态; 管片结构安全系数沿圆周分布不均,拱顶安全系数小于其他位置,管片结构的安全系数为2.12-2.91,设计满足安全性要求。

关键词: 综合管廊, 水下盾构隧道, 管片结构, 原型试验, M-N承载力曲线, 安全性评估

Abstract: In order to verify the safety of segment structure of large crosssection shield tunnel under high water pressure, 5 control crosssections of Sutong GIL utility tunnel project are selected as the research object to carry out prototype loading test on the segment structure by multifunctional shield tunnel structure loading device. Based on the theory of eccentric compression ultimate bearing capacity of concrete structure, MN bearing capacity curve of segment structure is derived, and safety evaluation index of segment structure is put forward. The research results show that: (1) The bending moment of the segment structure shows a butterflyshaped distribution, and the axial force shows a circularshaped distribution; the maximum positive bending moment and the maximum axial force appear on the crown. (2) The test internal forces of the segment structure of selected 5 control crosssections are all within the envelope of the bearing capacity curve, which is in a safe state. (3) The safety coefficient of the segment structure is unevenly distributed along the circumference; the safety coefficient of crown is smaller than other positions; the safety coefficient of segment structure ranges from 2.12 to 2.9, which meets safety requirements.

Key words: utility tunnel, underwater shield tunnel, segment structure, prototype test, MN bearing capacity curve, safety assessment

中图分类号: