To reduce the probability
of breakdown due to the gap between the water column formed by the seepage of
water from tunnel crown and the cantilever insulator, and improve the stability
of the power supply system in the tunnel, a seepage deflector structure that
can change the location of seepage water falling from the crown is designed,
and its effect on the electric field near the cantilever insulator is analyzed.
A 1∶1 three-dimensional
model containing crown, water column, and cantilever insulator is constructed
and its potential and electric field distributions are calculated, thus
examining the effects of water column morphology, water column length, water
column position, and inflow channel structure on the spatial electric field
distribution in the vicinity of the insulator. The results reveal the
following: (1) When the water column is grounded at one end and intermittent,
its maximum air gap electric field distortion rate is less than that when the
water column channel is continuous. (2) When a continuous column of water
extending downwards from the crown drops 68 mm from the high-voltage end of the cantilever insulator, the average electric field
strength of the remaining air gap is less than 5.66 kV/cm. (3) The closer the
water column is to the low voltage end of the insulator, the smaller the
distortion rate of the electric field strength on the surface of the water
column. (4) The average electric field strength of the air gap from the crown
to the high-voltage fittings is lower than 5.23 kV/cm
after the addition of a deflector channel to change the drop point of the water
column.
SUN Wenxiong
,
MA Jianqiao
,
WU Youqiang
.
Influence of Crown Seepage on Electric Field Distribution Near Tunnel Cantilever Insulator and Seepage Deflector Channel Design
[J]. Tunnel Construction, 2024
, 44(S2)
: 309
-318
.
DOI: 10.3973/j.issn.2096-4498.2024.S2.030