ISSN 2096-4498

   CN 44-1745/U

二维码

Tunnel Construction ›› 2018, Vol. 38 ›› Issue (S1): 73-78.DOI: 10.3973/j.issn.2096-4498.2018.S1.012

Previous Articles     Next Articles

An Experimental Study of Fire Protection and Control of Low Pressure Water Mist in Highway Tunnel

LI Hao1, CHEN Xinwen2, SHI Xiaolong3, WANG Yaohong3, ZHU Ronghua3, JIANG Wei3   

  1. (1. Yunnan Broadvision Engineering Consultants, Kunming 650228, Yunnan, China; 2. Yunnan Zhaohui Expressway Construction Head quarters, Kunming 650200, Yunnan, China; 3. Hefei KDLian Safety Technology Co., Ltd., Hefei 230088, Anhui, China)
  • Received:2017-05-23 Revised:2018-04-02 Online:2018-06-15 Published:2018-06-19

Abstract:

An onsite fire simulation experiment is conducted in Qiujiayakou Tunnel on Zhaohui Highway in Yunnan province to verify the performance of low pressure water mist fire extinguishing system to suppress fire spreading and expending during early fire in tunnel. During the experiment, the temperature and gas fields after low water mist spraying are measured; and fire protection and control performance of low pressure water mist in tunnel fire is studied. The quantitative test data obtained from the fire simulation experiment show that fire flame has been controlled, the temperature field around fire source has been reduced, the concentration of CO reduced rapidly after reaches peak value, and concentration of O2 kept approximately 21% during experiment, which can guarantee the fire safety and evacuation of personnel.

Key words: highway tunnel, low pressure water mist fire extinguishing system, fire

CLC Number: