隧道建设(中英文) ›› 2026, Vol. 46 ›› Issue (10): 2132-2146.DOI: 10.3973/j.issn.2096-4498.2026.10.006

• 研究与探索 • 上一篇    下一篇

极寒地区倾斜巷道空气温度沿程预测方法及控制因素

赵祎琪1, 丁希嘉1, 张恒1, *, 沙马小红1, 蒋福建2, 魏杰3   

  1. (1. 西南交通大学 极端环境岩土和隧道工程智能建养全国重点实验室, 四川 成都 610031; 2. 西南交通大学机械工程学院, 四川 成都 610031; 3. 中国电建集团中南勘测设计研究院有限公司, 湖南 长沙 410014)
  • 出版日期:2026-10-20 发布日期:2026-10-20
  • 作者简介:赵祎琪(2000—),女,四川泸州人,西南交通大学机械专业在读博士,研究方向为隧道温度场分布特性及通风设计。 E-mail: zhaoyiqi2022200052@myswjtu.edu.cn。 *通信作者: 张恒, E-mail: tunnelzh@home.swjtu.edu.cn。

Method for Predicting Airflow Temperature Along Length of Inclined Tunnels in Extreme Cold Conditions and Controlling Factors

ZHAO Yiqi1, DING Xijia1, ZHANG Heng1, *, SHAMA Xiaohong1, JIANG Fujian2, WEI Jie3   

  1. (1. National Key Laboratory of Intelligent Construction and Maintenance of Geotechnical and Tunnel Engineering in Extreme Environments, Southwest Jiaotong University, Chengdu 610031, Sichuan, China; 2. Institute of Mechanical Engineering, Southwest Jiaotong University, Chengdu 610031, Sichuan, China; 3. PowerChina Zhongnan Engineering Corporation Limited, Changsha 410014, Hunan, China)
  • Online:2026-10-20 Published:2026-10-20

摘要: 为解决极寒地区倾斜巷道受外界冷风侵入引发的施工环境恶化、洞内冻害频发等工程难题,以极寒环境下倾斜巷道空气温度场为研究对象,采用现场监测、理论推导与三维数值模拟相结合的方法,系统揭示洞口冷风侵入条件下倾斜巷道纵向空气温度的时空演变规律,并明确温度分布主控因素。首先,在巷道0~1 000 m布设多断面监测点,获取极寒条件下倾斜巷道内空气温度沿程分布特征;然后,基于Boussinesq近似与准稳态湍流自然对流假设,修正流体力学与传热学控制方程,引入瑞利数Ra与努塞尔数Nu关联式,考虑下坡坡度对浮力项的修正,推导得到倾斜巷道内空气温度沿程预测模型;最后,利用Fluent建立全尺寸三维模型,对冷风侵入动态过程开展仿真,并通过现场监测数据进行模型验证,模型计算温度与实测温度最大偏差3 ℃,冻结长度误差20%。结合推导的空气温度沿程预测模型,采用多工况参数分析与标准化回归系数法,系统研究巷道进风风速、进风风温、壁面温度、下坡坡度及断面设计参数对空气温度沿程变化规律的影响权重。结果表明: 1)极寒条件下巷道空气温度沿纵向呈指数回升趋势,冷空气沿断面下部侵入形成底部低温区与中部对流混合区; 2)进风风温、进风风速对空气温度平均变化率呈显著负向影响,壁面温度呈显著正向影响,巷道断面设计参数与下坡坡度影响不显著; 3)标准化回归分析显示,各因素可解释空气温度平均变化率95.1%的原因,其中进风风温影响程度最大; 4)所构建的温度预测模型精确可靠,可准确预估极寒地区倾斜巷道空气温度分布。

关键词: 寒区倾斜巷道, 空气温度场, 现场监测, CFD 数值模拟, 温度预测模型, 标准化回归, 湍流对流修正

Abstract: The construction of inclined tunnels in extremely cold regions can deteriorate the construction environment and cause frequent frost damage inside tunnels due to cold-air intrusion. To address these challenges, field monitoring, theoretical derivation, and three-dimensional numerical simulation were employed to systematically investigate the spatiotemporal evolution of longitudinal airflow temperature in inclined tunnels subjected to cold-air intrusion through the portal and to identify the main factors controlling temperature distribution. Monitoring sections were arranged along a 0-1 000 m stretch of the tunnel to characterize the longitudinal distribution of air temperature. Based on the Boussinesq approximation and the assumption of quasi-steady turbulent natural convection, the governing equations for fluid flow and heat transfer are modified. Correlations involving the Rayleigh and Nusselt numbers were incorporated, and the buoyancy term was corrected to account for the tunnel inclination angle, yielding a longitudinal airflow temperature prediction model suitable for inclined tunnels. A full-scale, three-dimensional numerical model was established using FLUENT to dynamically simulate the cold-air intrusion process, and its accuracy was validated against field monitoring data. The maximum deviation between simulated and measured temperatures was 3 ℃, and the error in predicting the freezing length was 20%. Based on the prediction model, a parametric analysis was conducted under multiple conditions, and the standardized regression coefficient method was used to quantify the effects of inlet air velocity, inlet air temperature, wall temperature, tunnel inclination angle, and cross-sectional characteristics on longitudinal air temperature variations. The results show the following: (1) The airflow temperature in extremely cold tunnels exhibits an exponential recovery trend along the longitudinal direction. Cold air intrudes along the lower part of the tunnel cross section, forming a low-temperature zone at the bottom and a convective mixing zone in the middle. (2) Inlet air temperature and inlet air velocity have significant negative impacts on the rate of air temperature change, while wall temperature has a significant positive impact. In contrast, the effects of tunnel crosssectional dimensions and downward inclination are not significant. (3) The standardized regression analysis shows that the selected factors explain 95.1% of the variation in the rate of air temperature change, with inlet air temperature exerting the greatest influence. The proposed temperature prediction model demonstrates reliable accuracy and can accurately predict air temperature distributions in inclined tunnels in extremely cold regions. The findings provide a theoretical basis and technical support for construction ventilation design, the development of frost-prevention and thermal insulation measures, and safety management in underground engineering projects in cold regions.

Key words: inclined tunnel in cold region, airflow temperature field, field measurement, computational fluid dynamics numerical simulation, temperature prediction model, standardized regression, turbulent convection